Live Loads on Buried Pre-Insulated Pipe
| Height of Cover |
LIVE LOAD TRANSFERRED TO PRE-INSULATED PIPE |
| Highway H20*1 |
Railway E80*2 |
Airport*3 |
| mm |
ft |
kPa |
lbs/in2 |
kPa |
lbs/in2 |
kPa |
lbs/in2 |
| 300 |
1 |
86.19 |
12.50 |
- |
- |
- |
- |
| 600 |
2 |
38.34 |
5.56 |
181.96 |
26.39 |
90.60 |
13.14 |
| 900 |
3 |
28.75 |
4.17 |
162.79 |
23.61 |
84.67 |
12.28 |
| 1200 |
4 |
19.17 |
2.78 |
126.87 |
18.40 |
77.71 |
11.27 |
| 1500 |
5 |
12.00 |
1.74 |
114.94 |
16.67 |
69.57 |
10.09 |
| 1800 |
6 |
9.58 |
1.39 |
107.77 |
15.63 |
60.61 |
8.79 |
| 2100 |
7 |
8.41 |
1.22 |
83.77 |
12.15 |
54.13 |
7.85 |
| 2400 |
8 |
4.76 |
0.69 |
76.60 |
11.11 |
47.78 |
6.93 |
| 3000 |
10 |
- |
- |
52.68 |
7.64 |
42.80 |
6.09 |
| 3600 |
12 |
- |
- |
38.34 |
5.56 |
32.82 |
4.76 |
Urecon’s standard polyethylene jacket is suitable for H-20 highway loading at 600 mm (24 in). Live H-20 load transferred to the insulation a6 600 mm (24 in) depth of bury is 38kPA (5.51 lbs/in2). Our system is rated at 414 to 552 kPA (60-80 lbs/in2).
|