Urecon Pre-Insulated Pipe | Return to Home

Home | Career Opportunities | Contact | Search:

Applications Systems Heat Tracing Documents Learning Centre About URECON
 
 
null
                     

                    Urecon | Celebrating 40 Years | 1969-2009

                    Live Loads on Buried Pre-Insulated Pipe

                    Height of Cover LIVE LOAD TRANSFERRED TO PRE-INSULATED PIPE
                    Highway H20*1 Railway E80*2 Airport*3
                    mm ft kPa lbs/in2 kPa lbs/in2 kPa lbs/in2
                    300 1 86.19 12.50 - - - -
                    600 2 38.34 5.56 181.96 26.39 90.60 13.14
                    900 3 28.75 4.17 162.79 23.61 84.67 12.28
                    1200 4 19.17 2.78 126.87 18.40 77.71 11.27
                    1500 5 12.00 1.74 114.94 16.67 69.57 10.09
                    1800 6 9.58 1.39 107.77 15.63 60.61 8.79
                    2100 7 8.41 1.22 83.77 12.15 54.13 7.85
                    2400 8 4.76 0.69 76.60 11.11 47.78 6.93
                    3000 10 - - 52.68 7.64 42.80 6.09
                    3600 12 - - 38.34 5.56 32.82 4.76

                    Urecon’s standard polyethylene jacket is suitable for H-20 highway loading at 600 mm (24 in).  Live H-20 load transferred to the insulation a6 600 mm (24 in) depth of bury is 38kPA (5.51 lbs/in2).  Our system is rated at 414 to 552 kPA (60-80 lbs/in2).

                    Notes:

                    1. Simulates 20 ton traffic and impact.
                    2. Simulates 119,000 Kg/m (80,000 lb/ft) railway load and impact.
                    3. Simulates 81,650 Kg (180,000 lb) gear assembly, 660 mm (26 in) spacing between tires and 1.676 mm (66 in) center to center spacing between fore and aft tires, under a rigid pavement 300 mm (12 in) thick plus impact.
                    4. Source: IPEX Inc.